Mitsubishi Electric MELSEC iQ-R Series User Manual page 165

Melsecnet/h network module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SW007C
Parameter error status
to
SW007F
SW0080
CPU moderate to major
to
error occurrence status
SW0083
SW0084
CPU operating status
to
SW0087
Description
Stores the parameter error status of each station.
Off: Normal
On: Error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW007C
16 15 14 13 12 11 10
SW007D
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW007E
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW007F
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
Each number in the table represents a station number.
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
• Reserved stations and stations exceeding the maximum station number are ignored.
Stores the moderate/major error occurrence status of the CPU module on each station.
(Including own station)
Off: No moderate/major error
On: Moderate/major error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0080
16 15 14 13 12 11 10
SW0081
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0082
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0083
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
Each number in the table represents a station number.
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
• This register is enabled only for normally operating stations in 'Baton pass status'
(SW0070 to SW0073).
• Reserved stations and stations exceeding the maximum station number are ignored.
Stores the CPU RUN state of each station. (Including own station)
Off: RUN, STEP-RUN
On: STOP, PAUSE, or a moderate or serious error occurring
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW0084
16 15 14 13 12 11 10
SW0085
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW0086
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW0087
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
Each number in the table represents a station number.
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
• This register is enabled only for normally operating stations in 'Baton pass status'
(SW0070 to SW0073).
• Reserved stations and stations exceeding the maximum station number are ignored.
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
Appendix 4 List of Link Special Register (SW) Areas
Availability
Control
Normal
station
Station
A
APPX