Station-based block data assurance
The cyclic data is assured for each station by handshake between the CPU module and RJ71LP21-25 for a link refresh.
■Setting method
To enable station-based block data assurance, set "Enable" under "Supplementary Cyclic Settings" in "Application Settings"
of the control station. (Page 65 Supplementary Cyclic Settings)
Once this setting is enabled on the control station, the data for all stations is assured for each station.
■Access to link devices
During a link refresh, data are assured for each station as shown below.
CPU module
Device
Data
Station No.1
assurance
Data
Station No.2
assurance
Data
Station No.3
assurance
Data
Station No.4
assurance
• Since station-based block data assurance is only applied for link refresh processing, configure an interlock
when using the direct access to link devices (J\ specification).
• When the send/receive data station-based block data assurance is set to "Enable", refer to the following
description for the formula to calculate transmission delay time. ( Page 175 Processing Time)
• If the network is configured with the MELSECNET/10 mode, station-based block data assurance is disabled
for the ACPU/QnACPU installed stations. Configure an interlock by the program for the ACPU/QnACPU
installed stations. ( Page 79 Precautions for Programming)
RJ71LP21-25
Link device
Station No.1
Station No.2
Link refresh
Station No.3
Station No.4
Data
assurance
Data
assurance
Data
assurance
Data
assurance
1.1 Cyclic Transmission Function
1
1 FUNCTIONS
31