Mitsubishi Electric MELSEC iQ-R Series User Manual page 59

Melsecnet/h network module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
LB/LW
LB
Points
Setting
Start
End
LW
Points
Start
End
Low
Points
Speed
LB
Start
End
Low
Points
Speed
LW
Start
End
Description
Set the number of points (decimal) of LB sent by each station. Set in
increments of 16 point.
Set the start number of the LB range to be sent by each station. Set in
multiples of 16 including 0.
Set the end number of the LB range to be sent by each station. Set in
multiples of 16-1.
Set the number of points (decimal) of LW sent by each station.
Set the start number of the LW range to be sent by each station.
Set the end number of the LW range to be sent by each station.
Set the number of points (decimal) of low speed LB sent by each station. Set
in increments of 16 point.
Set the start number of the low speed LB range to be sent by each station.
Set in multiples of 16 including 0.
Set the end number of the low speed LB range to be sent by each station.
Set in multiples of 16-1.
Set the number of points (decimal) of low speed LW sent by each station.
Set the start number of the low speed LW range to be sent by each station.
Set the end number of the low speed LW range to be sent by each station.
Setting range
• MELSECNET/H mode: 16 to 16000
• MELSECNET/H extended mode: 16 to
16384
• MELSECNET/10 mode: 16 to 8192
Default: Blank
• MELSECNET/H mode, MELSECNET/
H extended mode: 0000H to 3FF0H
• MELSECNET/10 mode: 0000H to
1FF0H
Default: Blank
• MELSECNET/H mode, MELSECNET/
H extended mode: 000FH to 3FFFH
• MELSECNET/10 mode: 000FH to
1FFFH
Default: Blank
• MELSECNET/H mode: 1 to 1000
• MELSECNET/H extended mode: 1 to
16384
• MELSECNET/10 mode: 1 to 1000
Default: Blank
• MELSECNET/H mode, MELSECNET/
H extended mode: 0000H to 3FFFH
• MELSECNET/10 mode: 0000H to
1FFFH
Default: Blank
• MELSECNET/H mode, MELSECNET/
H extended mode: 0000H to 3FFFH
• MELSECNET/10 mode: 0000H to
1FFFH
Default: Blank
16 to 8192
Default: Blank
2000H to 3FF0H
Default: Blank
200FH to 3FFFH
Default: Blank
1 to 1000
Default: Blank
2000H to 3FFFH
Default: Blank
2000H to 3FFFH
Default: Blank
2 PARAMETER SETTINGS
2.2 Required Settings
2
57