Mitsubishi Electric MELSEC iQ-R Series User Manual page 161

Melsecnet/h network module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SW004A
Data link stop request
station
SW004B
CPU status of own station
SW004D
Link start result of own
station
SW004F
Link stop result of own
station
SW0051
System link start results
SW0053
System link stop results
SW0054
Parameter information
Description
Stores the station number of the station that performed the data link stop request for the
own station.
The data link stop request is performed by 'System link stop' (SB0003).
...
...
b15
b14
b7
b6
b0
...
...
SW004A
0
0
b6 to b0: Station number
• 0: Own station
• 1 to 64: Another station
b15: Specified station
• 0: Station number specified
• 1: All stations specified
(Conditions)
• This register is enabled when 'Cause of data link stop' (SW0049) is 01H.
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
Stores the status of the CPU module of the own station.
0: Normal
1 or greater: Error (An error code is stored.)
Stores the results when link is started by 'Link startup of own station' (SB0000).
0: Completed normally
1 or greater: Completed with an error (An error code is stored.)
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
Stores the results when link is stopped by 'Link stop of own station' (SB0001).
0: Completed normally
1 or greater: Completed with an error (An error code is stored.)
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
Stores the results when link is started by 'System link start' (SB0002).
0: Completed normally
1 or greater: Completed with an error (An error code is stored.)
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
Stores the results when link is stopped by 'System link stop' (SB0003).
0: Normal
1 or greater: Completed with an error (An error code is stored.)
(Conditions)
• This register is enabled when 'Baton pass error status of own station' (SB0047) is off.
When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior
to error is held.
Stores parameter information.
...
b15
b14
b13
b2
b1 b0
...
SW0054
0
0
0
b1 to b0: Type
• 00: Only common parameter is used (fixed at 00)
b15: MELSECNET/H
• 0: Not specified
• 1: Specified
When 'Receive parameter error' (SB0055) is on, the value is "000FH".
(Conditions)
• This register is enabled when 'Receive parameter error' (SB0055) is off.
Appendix 4 List of Link Special Register (SW) Areas
Availability
Control
Normal
station
Station
A
APPX
159