Setting method
Assign the link devices under "Network Range Assignment" in "Required Settings". (Page 55 Network Range
Assignment)
The link refresh is assigned under "Link Refresh Settings" in "Basic Settings". ( Page 61 Link Refresh Settings)
• Any station can be set as the I/O master station regardless of the station type of the control station or normal
station.
• The setting range of X and Y for LX and LY communication is the device range after the actual I/O of the
own station (1000 or greater is recommended for X/Y). When using multiple network modules (CC-Link IE
TSN, CC-Link IE Controller Network, CC-Link IE Field Network, MELSECNET/H, and CC-Link) or when
using two I/O master stations, assign the device ranges so that they do not overlap.
Actual I/O
Block I/O master station 1
Block I/O master station 2
No overlap assignment
1 FUNCTIONS
1.1 Cyclic Transmission Function
1
19