Communications

10.3 Transfer of diagnostic alarms to the controller

10.3
Transfer of diagnostic alarms to the controller
10.3.1

Transferring diagnostic alarms to the controller: PROFINET

Diagnostics alarms
Diagnostics alarms are transferred as diagnostic interrupts using the channel diagnostics
(identifier 8000h) as the diagnostic type.
The PROFINET device identification number is required for identifying a diagnostic interrupt.
The HCS4200 has the identification number 1003h.
The evaluation in SIMATIC is performed via I/O_FLT1 (OB82) and RALRM (SFB54).
Structure of the diagnostics alarm
Channel diagnosis comprises 6 bytes:
Byte
0,1
2
3
4,5
102
Description
Channel number
The following applies for channel numbers:
Channel number = 0: Diagnostic information relates to one module (CIM, POM,
PM)
Channel numbers <> 0: Diagnostic information relates to one channel (for POM,
PM only)
The power channel numbers are counted across the entire HCS.
Channel type, fault type
Data format
Error code (see Manufacturer-specific error codes (Page 104))