Technical specifications
13.4 Technical specifications for I/O module
Mechanical data:
Mounting position
Mounting type
Type of ventilation
Vibration resistance
during operation / acc. to IEC 60068-2-6
during storage / acc. to IEC 60068-2-6
Shock resistance
acc. to IEC 60068-2-27
acc. to IEC 60068-2-29
Protection class IP
Depth
Height
Width
Electromagnetic compatibility:
EMC emitted interference
Conducted interference / due to burst / acc. to IEC 61000-4-4
Conducted interference / due to surge / acc. to IEC 61000-4-5
Conducted interference / due to high-frequency radiation / acc. to IEC
61000-4-6
Field-bound parasitic coupling / acc. to IEC 61000-4-3
Electrostatic discharge / acc. to IEC 61000-4-2
Overvoltage category
138
vertical
Screw mounting to CIM
Forced ventilation
10 ... 58 Hz / 0.075 mm. 58 ... 150 Hz / 1 g
5 ... 8.5 Hz / 3.5 mm. 8.5 ... 500 Hz / 1 g
15g / 11 ms / 3 shocks / axis
25 g / 6 ms / 1000 shocks / axis
IP20
110 mm
141 mm
27 mm
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
2 kV signal cables
Voltage measurement inputs: 1 kV balanced, 2
kV unbalanced
10 V (0.15 ... 80 MHz)
10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
4 kV contact discharge / 8 kV air discharge
III