17.4.6 Current Value Update Data Area

For changing the current values for each axis that are managed by the positioning unit, store the
changed coordinate in this area and turn on the current value update request flag.
Offset
Bank
Name
address
Current value
0C0H
update request
flag
Current value
0C8H
update
00H
coordinate of
0C9H
axis 1
Current value
0CAH
update
coordinate of
0CBH
axis 2
Current value
0CCH
update
coordinate of
0CDH
axis 3
Current value
0CEH
update
coordinate of
0CFH
axis 4
17-16
Descriptions
Only when the corresponding bits to each axis changes to 1 from 0, the
current value managed in the positioning unit will be changed to the
following current value.
Afther the change, the positioning unit clears the corresponding bits to 0
automatically.
Store the coordinate to perform the current value update for axis 1.
Store the coordinate to perform the current value update for axis 2.
Store the coordinate to perform the current value update for axis 3.
Store the coordinate to perform the current value update for axis 4.