Huawei NetCol8000-C070 User Manual page 102

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
● User operator can access customer and delivery parameters. The parameters
on the Advanced menu are delivery parameters. User admin can access
customer, delivery, maintenance, and R&D parameters. The parameters on the
Advanced menu are R&D parameters.
● To prevent the effect of misoperations on the system, log in as user operator
before modifying parameters. Confirm with technical support before modifying
parameters which cannot be modified by user operator. Otherwise, the
supplier will not be liable for any consequences of the modification performed
by the user.
● Only certified professionals are allowed to modify the advanced parameters.
Unauthorized modifications may lead to device malfunction or damage.
● For system security purposes, change the preset password after the first login.
● After login, your permission will become invalid automatically if no operation is
performed for 3 minutes (configurable). For security purposes, tap
in the lower-right corner of the screen, and tap
corner of the screen to manually log out after you have completed all
operations.
Step 3 Set related parameters and tap Next until the home screen is displayed.
Table 4-2 Parameter description
Menu
Select
Language
Date & Time
Settings
Teamwork
Settings
Issue 07 (2021-12-30)
NO TICE
Parameter
/
Date format
Date settings
Time zone
Time
Teamwork group
No.
System address
Teamwork
function
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
or
Description
Specifies the display language.
Specifies the date format.
Specifies the time zone.
Specifies the time zone.
Specifies the time.
Specifies the planned teamwork group
number. This parameter should be the same
for all units in the same teamwork group.
Specifies the planned unit address. The
addresses of units in the same teamwork
group must be unique.
Specifies whether to enable the teamwork
function. Set this parameter based on onsite
heat load distribution.
● Disable: A unit operates independently.
● Enable: A unit operates in team with
other units.
in the upper-right
92