Figure 3-3 Layout of bottom pipe routing (1)
(1) NetCol8000-C
Figure 3-4 Layout of bottom pipe routing (2)
(1) NetCol8000-C
Issue 07 (2021-12-30)
NO TE
● The height of the raised floor for downflow units must be greater than 550 mm. (The
550 mm space under the floor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
● The height of raised floors is greater than 300 mm for upflow units.
● W indicates the distance between smart cooling products. The minimum W for upflow
units is 300 mm, and the minimum W for downflow units is 500 mm.
● L indicates the front maintenance distance, and the minimum L is 900 mm. If this
requirement cannot be met, the minimum L after front doors are removed can be 800
mm.