NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 07 (2021-12-30)
Name
Return air temp
to forcibly start
cooling
Cold aisle temp
to forcibly start
cooling
DO association
Cooling capacity
management
function
Floor water
overflow alarm
action
In-cabinet water
overflow alarm
action
Backup power
supply
Copyright © Huawei Technologies Co., Ltd.
Parameter Description
Specifies the temperature
threshold for forcibly
starting the compressor
when the return air
temperature is higher than
the threshold.
Specifies the temperature
threshold for forcibly
starting the compressor
when the cold air
temperature is higher than
the threshold.
● Smoke & Water only:
When a smoke sensor
alarm or water overflow
alarm is generated, the
common alarm 1 dry
contact is closed.
Common alarm 2 does
not work.
● Critical & Major alarm:
When a critical alarm is
generated, the common
alarm 1 dry contact is
closed. When a major
alarm is generated, the
common alarm 2 dry
contact is closed.
● No: The common alarm
1 and 2 dry contacts are
open and no alarms are
reported.
The cooling capacity
management function can
be set to Enable or
Disable.
Shutdown, Inactivity,
Only indoor fan running,
or Humidifier stopped can
be set as required.
Shutdown, Inactivity,
Only indoor fan running,
or Humidifier stopped can
be set as required.
-
E Parameter Description
Default Value
43.0°C
27.0°C
Smoke &
Water only
Disable
Shutdown
Humidification
stopped
Normal
239