Setting Communications Parameters (Snmp Protocol) - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Table 4-8 Modbus TCP parameter settings
Parameter
Link mode
Client
encryption
Server
encryption
NMS IP
address
NMS port
number
Pre-shared
password
----End

4.5.4.4 Setting Communications Parameters (SNMP Protocol)

Context
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > SNMP Settings. The
screen shown in
Issue 07 (2021-12-30)
Setting
Server,
Client, Server
and client
Enable,
Disable
Enable,
Disable
-
-
To set communications parameters, log in as the admin user.
This section is suitable only for SNMP. Skip this section if you use Modbus.
Record the values entered in this section which will be needed when you
access a smart cooling product to an NMS.
One smart cooling product supports concurrent access of up to 6 EMSs
through SNMP.
Figure 4-10
Copyright © Huawei Technologies Co., Ltd.
Setting Method
● If you set Link mode to Server, the smart
cooling product, as a server, supports two client
connection and establishes communication.
● If you set Link mode to Client, the smart
cooling product, as a client, can connect to a
remote server and establish communication.
● If you set Link mode to Server and client, the
smart cooling product, as a server, supports two
client connection and establishes
communication. In addition, the smart cooling
product, as a client, can connect to a remote
server and establish communication.
This parameter is configurable when Link mode is
set to Client.
This parameter is configurable when Link mode is
set to Server.
Enter the actual IP address of the NMS. IP
addresses of the display panel, NMS client, and
NMS server must be unique. This parameter is
configurable when Link mode is set to Client.
It is recommended that you retain the default
value. If you need to change the value, enter a
value as required. This parameter is configurable
when Link mode is set to Client.
Secondary authentication password used for
Modbus-TCP connection.
is displayed.