Huawei NetCol8000-C070 User Manual page 94

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Context
Adjust the shutter angle as required. Normally, keep the shutter horizontal. To
specifically cool the near-end devices, you can adjust the shutter angle to some
degrees downward so that the cold air can cool the device directly. It is
recommended that the angle downward should not exceed 30 degrees to avoid
that part of the cold air flows back to the smart cooling product, affecting the
cooling effects.
Procedure
Step 1 Remove the cap front panel using a Phillips screwdriver. Place the cap on the top
of the cabinet.
It takes two persons to install the cap using a 2 m step ladder.
Issue 07 (2021-12-30)
Figure 3-59 Cap Introduction (Unit: mm)
Table 3-12 Cap dimensions
Upflow Units
Upflow Units
Model
Dimensions (H x W
x D) (mm)
NetCol8000-
2000×900×1000
C070U
NetCol8000-
2000×1800×1000
C130U
NetCol8000-
2000×2700×1000
C190U
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Cap Dimensions (H
x W x D) (mm)
600×900×1000
600×900×1000
600×900×1000
3 Installation
Cap
Quantity
(PCS)
1
2
3
84