How To Commission Single Component - Huawei NetCol8000-C070 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 7-17 Setting alarm parameter 1
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
Figure 7-18 Setting alarm parameter 2
----End

7.4.14 How to Commission Single Component

Context
Procedure
Step 1 Choose Maint > Diagnostic Mode > Enter.
Issue 07 (2021-12-30)
On the diagnostic mode screen, you can turn on or off components, and
control their output ratio.
If you need to manually turn on or off system components in diagnostic
mode, ensure that the smart cooling product is started before operation.
Take commissioning the indoor fan as an example.
Copyright © Huawei Technologies Co., Ltd.
, as shown in
Figure
7-18.