Huawei NetCol8000-C070 User Manual page 104

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
System
Settings
Issue 07 (2021-12-30)
Parameter
Hot aisle
temperature and
humidity sharing
Motorized
damper
Dual power
supply setting
Require password
to start or
shutdown onsite
Dehumidifying
function
DO_1 action
DO_2 action
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Description
This function can be enabled only when at
least one smart cooling product in the
group is equipped with hot aisle T/H
sensors. If this function is enabled, the
master unit in the teamwork group collects
the hot aisle temperature and humidity
values from all units equipped with hot aisle
sensors, and synchronizes the temperature
and humidity values to all units after logical
calculation.
After this function is enabled, the master
unit synchronizes the temperature and
humidity control type and setpoints to all
slave units.
● Disable: The air damper function of the
unit is disabled.
● AO Ctrl: Select AO Ctrl for AO-type air
dampers.
Set this parameter as required.
● Primary power only: Select this option
when the dual-power model is connected
to the primary power only.
● Primary power first: Select this option
when the dual-power model is connected
to two power supplies.
● No: No password is required for startup
or shutdown.
● Yes: A password is required for startup
and shutdown.
● Enable: The device starts dehumidifying
when the ambient humidity is higher
than the humidity setpoint.
● Disable: The dehumidifying function is
disabled.
This parameter can be set to On or Off, and
is used together with DO_1. For details, see
DO_1 description.
This parameter can be set to On or Off, and
is used together with DO_2. For details, see
DO_2 description.
94