ABB SACE Emax 2 Series Operating Instructions Manual page 157

Low voltage air circuit-breaker
Table of Contents

Advertisement

154 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
4.
Extract the disconnection crank from its housing See Figure 57.
5.
Press the lock pushbutton and fit the handle into the moving part. In this phase, the moving part
will still be in the DISCONNECT position. See Figure 58.
Figure 57
6.
Keep breaker pushed. Turn the crank clockwise until the pushbutton comes out and the indicator
shows that the circuit-breaker is in TEST position. See Figure 59.
Figure 59
7.
Press the lock button and then rotate the crank clockwise until the button comes out and the
indicator shows that the circuit-breaker is in the CONNECT position. See Figure 60.
Figure 60
2
Figure 58
1
2
2
ABB | SACE Emax 2
1
1
Continued on the next page
Mechanical characteristics
1 - E1.2 description

Advertisement

Table of Contents
loading

Table of Contents