ABB SACE Emax 2 Series Operating Instructions Manual page 224

Low voltage air circuit-breaker
Table of Contents

Advertisement

Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Certain additional information concerning the version and status of the module is available via the service
221 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
is available in the Settings menu (page 49).
Two areas are activated if Ekip Touch detects the module correctly:
• information area in the About - Modules menu, containing the software version and serial number
of the module
• specific configuration area in the Settings - Modules menu, where the following communication
parameters can be configured:
Parameter
Description
Module address; 1 to 63 range available
MAC Address
IMPORTANT: devices connected to the same network must
have different addresses
Data transmission speed; 3 options are available: 125 kbit/s, 250
Baudrate
kbit/s, 500 kbit/s
63 default of the Ekip Com DeviceNet
(1)
Redundant module
communication:
Parameter
Description
Class ID
Defines the addressing class of the module, either 8 or 16 bits.
Defines the behavior of the module following loss of
communication (Bus-Off), with a choice between Standard
Bus-Off
(supply reset is awaited if the communication is lost) and
Behavior
Advanced (the module attempts to reset itself if it detects the
error status).
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).
module; 62 default of the Ekip Com DeviceNet
TM
ABB | SACE Emax 2
Default
63 / 62
(1)
125 kbit/s
TM
Default
8-bit Class ID
DeviceNet
standard
External electronic accessories
4 - Ekip Com DeviceNet TM