M: Motor The motor automatically recharges the closing springs of the circuit-breaker when these are discharged.
195 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
The motor is equipped with a limit contact S33 M/1 that interrupts the power supply of the motor after
charging of the springs is completed.
The motor is equipped with a limit contact S33 M/2 that signals the state of the charged springs.For
information on the S33 M/2 limit contact refer to the dedicated paragraph "S33 M/2: springs charged
signalling contact" in this chapter.
M for E1.2
M for E2.2 - E4.2 - E6.2
NOTE: The closing springs can in any case be charged manually through the appropriate
front control lever.
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24...30 V AC/DC
48...60 V AC/DC
100...130 V AC/DC
220...250 V AC/DC
Available voltages (Un)
(1)
380...415 V AC
Available voltages (Un)
(2)
277 V AC/DC
380...400 V AC
440...480 V AC
for E1.2
(1)
(2)
for E2.2 - E4.2 - E6.2
M: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet
kit sheet 1SDH001000r0609.
U1
U2
M
U1
U2
M
General characteristics
Operating limits
Inrush power (Ps)
Power during charge (Pc):
Charging time
1SDH000999r0609
ABB | SACE Emax 2
85...110 %Un
500 VA/W
100 VA/W
Min 5 s, max 10 s
and for E2.2-E4.2-E6.2 in the
Electrical accessories
1 - Electrical control accessories