7 - Default parameters

37 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
The Ekip Dip trip units are supplied with the following default parameters, some adjustable with the front
DIPs (protections, Frequency, Neutral), other via front bus.
Protection/Parameter
L
S
(1)
I
G
(1)
Frequency
Neutral
Hardware Trip
Local Bus
LED Alive
Maintenance
S Protection available with LSI and LSIG versions of the trip unit. G Protection available with LSIG
(1)
version.
Value
1 In; 144 s
Off; 0.1 s
4 In
Off; 0.1 s
50 Hz (IEC) / 60 Hz (UL)
Off (for three-pole circuit breakers).
50 % (for four-pole circuit-breaker)
Disabled
Off
Disabled (Power-on LED fixed)
Off
ABB | SACE Emax 2
Ekip Dip