Ekip Com Hub - ABB SACE Emax 2 Series Operating Instructions Manual

Low voltage air circuit-breaker
Table of Contents

Advertisement

10 - Ekip Com Hub

Safety and cyber security The module uses the HTTPS protocol and can be connected to the Internet
Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply , either on the
Power supply Ekip Com Hub is supplied directly by the Ekip Supply module to which it is connected.
240 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Ekip Com Hub is a communication accessory that enables the data and measurements of Ekip Touch and
other devices connected to the same installation to be gathered and then made available on the server
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document,
which contains all the details. (page 179).
The ports used by the module are:
Port
Service
67/udp 68/udp
DHCP client
443/tcp
HTTPS
123/udp
SNTP
53/udp
DNS
The Ekip Com Modbus RTU and Ekip Com Modbus TCP modules can be configured to support Ekip Com
Hub in the collection of data to send to Cloud. See Getting Started 1SDC200063B0201.
Ekip Com Hub is always supplied with contacts Ekip AUP and Ekip RTC (page 258).
If connected to a withdrawable version of the circuit-breaker, it is possible to detect the racked-in/racked-
out status
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the case
may be). The plant manager must establish and maintain appropriate measures (such as
but not limited to the installation of firewalls, application of authentication measures,
encryption of data, installation of antivirus programs, etc.) to protect the product,
the network, the customer system and interface against any kind of security breaches,
unauthorized access, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security
breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or
information.
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Notes
DHCP client enabled alternatively as Static address = On
Always active when module is enabled
Active with SNTP client enabled
Always active
ABB | SACE Emax 2
External electronic accessories
10 - Ekip Com Hub