KLP lock additional accessory This additional accessory limits the blocking function to the disconnected position only.
SL: shutter lock The SL shutter locks the shutters of the fixed part.
DLC: Door opening lock with
the circuit-breaker in closed
position
188 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet
kit sheet 1SDH001000r0727.
It is possible to lock the upper and lower shutters independently.
This is an accessory available on all the fixed parts and can work with the aid of padlocks with diameters
of 4 mm - 5/32", 6 mm - 1/4", 8 mm - 5/16", with a maximum of four padlocks per fixed part (two for the
upper shutters and two for the lower shutters).
NOTE: The padlocks are at customer's expenses.
SL for E1.2
The DLC prevents the following operations from being carried out:
• opening the switchgear door with the circuit-breaker closed if the circuit-breaker is in fixed version
• opening the switchgear door with the circuit-breaker closed and in connected position if the
circuit-breaker is in fixed version
• closing of the circuit-breaker when the switchgear door is open
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet
kit sheet 1SDH001000r0712.
for E2.2 - E4.2 - E6.2
1SDH000999r0727
and for E2.2-E4.2-E6.2 in the
SL for E2.2 - E4.2 - E6.2
1SDH000999r0712
and for E2.2-E4.2-E6.2 in the
Mechanical accessories
2 - Mechanical safety accessories
ABB | SACE Emax 2