Input parameters All the available inputs enable the following parameters to be configured:
Output parameters All the available inputs enable the following parameters to be configured:
Remote information Certain additional information concerning the version and status of the module is available via the service
246 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Menu The specific configuration area will activate in the Settings - Modules menu if the Ekip Signalling 2K
module is detected correctly by Ekip Touch.
A specific menu containing the submenus of all the available and configurable inputs and outputs is
available for each Ekip Signalling 2K module detected by Ekip Touch.
Parameter
Polarity
Delay
Parameter
Signal source
Delay
Contact Type
Latched
(1)
min Activation
Time
(2)
(1)
deactivate the latchings of the outputs used if the Measurement module is used for the Power
Controller function
if the Measurement module is used for the Power Controller function, the Power Controller option
(2)
will also be available; if selected, the output is kept activated for a set time that depends on the
function, regardless of whether the event that activated it persists
About The specific menu of the module available in the About - Modules menu contains:
• the serial number and version of the module
• the statuses of the inputs (On/Off) and outputs (Open/Closed)
Test The test area in the Test menu is activated if the Ekip Signalling 2K module is detected correctly.
For details of the test characteristics, please consult page 137.
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).
Description
Defines whether the input is interpreted as ON by Ekip Touch when
it is open ( Active open ) or when it is closed ( Active Closed )
Minimum activation time of the input before status change is
recognized; the delay is given in seconds and can be set within
range: 0 s to 100 s, in 0.01 s steps
NOTES:
• if the input is deactivated before this time has elapsed the
status change is not recognized
• if delay = 0 s status change must still be more than 300 µS
Description
Event which activates the output and switches the contacts.
Different protection proposals, statuses and thresholds are available
on the display; the Custom mode can be configured via Ekip Connect
so as to extend the solutions and combine several events
Minimum duration of the presence of the source before the output is
activated; the delay is given in seconds and can be set within range:
0 s to 100 s, in 0.01 s steps
NOTES:
• the output will not be switched if the source is deactivated
before this time has elapsed
• if delay = 0 s the source must still be present for longer than
300 µS
Defines the rest status of the contact with source not present
between: open (NO) and closed (NC)
Allows the output (and relative status led) to be kept activated (On)
or deactivated (Off) when the event disappears
Defines the minimum closing time of the contact following the rapid
presence of sources:
• Source duration < min. activation = contact is activated for the
minimum activation time
• Source duration ≥ min. activation = contact is activated for as long
as the source persists
Choose between: 0 ms, 100 ms, 200 ms
ABB | SACE Emax 2
Default
Active
closed
0.1 s
Default
None
0 s
NO
OFF
0 ms
External electronic accessories
11 - Ekip Signalling 2K