ABB SACE Emax 2 Series Operating Instructions Manual page 200

Low voltage air circuit-breaker
Table of Contents

Advertisement

AUX 6Q
: Additional open/
(1)
closed auxiliary contacts
197 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
The additional AUX 6Q contacts signal the open/closed state of the circuit-breaker.
These are "switching" contacts and are available in three types:
• six standard contacts
• six digital signals (low power)
• three standard contacts (Q1-Q2-Q3) + three digital signals (Q4-Q5-Q6)
61
51
62
52
64
54
Q5..Q10
Only for E2.2 - E4.2 - E6.2
(1)
NOTE: it is possible to order the AUX 6 Q contacts only if the circuit-breaker is not equipped
with a protection trip unit with the Ekip Signalling 4K module.
The following table provides information on the electrical characteristics:
Characteristics
24V
DC
125V
250V
Breaking
250V
capacity
AC
400V
Minimum load
AUX 6Q: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000r0601.
71
81
91
01
HC
H1
H2
H3
H4
72
82
92
02
HC
K3
K4
K5
K6
74
84
94
04
HC
K7
K8
K9
K10
EKI P S ignalling 4K
Standard
-
0.5A @ 0ms / 0.3A @ 10ms
0.3A @ 0ms / 0.15A @ 10ms
3A cosφ 0,3
5A cosφ 0,7
5A cosφ 1
3A cosφ 1
2A cosφ 0,7
1A cosφ 0,3
100mA @ 24V
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
-
1mA @ 5V
Electrical accessories
2 - Electrical signalling accessories