ABB SACE Emax 2 Series Operating Instructions Manual page 47

Low voltage air circuit-breaker
Table of Contents

Advertisement

Measurements
44 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Figure 14
If provided for by Trip unit model, the Measurements pages contain a list of measurements acquired in
real time, expressed in absolute value:
Page
Name
1
Current
2
Voltage
3
Active power
4
Reactive power
5
Apparent power
6
Energy counters
7
Power Controller
8
Load shedding
9
Ekip Signalling 3T
Ekip Touch configuration involves certain exceptions:
• the Ne current measurements are available with 4P and 3P + N configurations
• the phase voltage measurements are available with the 4P and 3P + active external neutral voltage
configuration
• with the 3P configuration, pages: Active Power, Reactive Power and Apparent Power are replaced
by the Powers page with the total active, reactive and apparent power measurements
• Ige/Rc current available with external toroid activated
• Power Controller page available with Power Controller function activated
• Load Shedding available with Load Shedding function activated
Press the sides of the display to browse the pages; press the HOME key to quit.
NOTE: each page can be set as the main page by pressing HOME , holding it for five seconds
and confirming the message on the display
Measurements
Currents: phase, earth fault, external earth fault/Rc
Voltages: line-to-line, phase, neutral
Phase and total active powers
Phase and total reactive powers
Phase and total apparent powers
Total active, reactive and apparent energies
Power Controller measurement summary, if installed
Summary of Load Shedding measurements, if present
Summary of Ekip Signalling 3T module measurements, if
installed
ABB | SACE Emax 2
Ekip Touch - Interface and menus
3 - Graphic pages