Performance Table - ABB SACE Emax 2 Series Operating Instructions Manual

Low voltage air circuit-breaker
Table of Contents

Advertisement

11 - Performance table

General notes:
Standard Protections
95 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
• The performance values given in the next table are valid with ≥ 100 ms trip time, temperature
and signals within the operating limits; failure to comply with these limitations could lead to an
increase in the tolerances.
• Ekip Touch sends the TRIP command if the signal read exceeds the threshold for longer than the
set time (or the time resulting from the calculation formula)
• with an inverse time-delay trip curve, the calculation refers to a signal with a constant value
throughout the timing: variation of the alarm signal causes a different trip time
• The additional notes are given after all the tables
Protection
Trip time t
[ANSI code]
(with curve t = k / I
L [49]
(with curves 60255-151)
t
= t2 ( with curve t =
t
k )
S [50TD / 51]
(with curve t = k / I
S2 [50TD]
t
= t5
t
I [50]
t
≤ 30 ms
t
t
= t4 ( with curve t =
t
k )
G [50N TD /
51N]
(with curve t = k / I
MCR
t
≤ 30 ms
t
2I [50]
(10)
IU [46]
t
= t6
t
Startup
Protection
Trip time t
[ANSI code]
S StartUp
t
= t2 startup
t
I StartUp
t
≤ 30 ms
t
G StartUp
t
= t4 startup
t
S2 StartUp
t
= t5 startup
t
Trip threshold
(1)
tolerance
(3)
t
Activation for If
)
2
within range: (1.05 to
1.2) x I1
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
)
2
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
± 10 %
± 7 %
2
)
± 10 %
± 10 %
± 10 %
Trip threshold
tolerance
(3)
t
with If ≤ 6 In: ± 7
% / with If > 6 In:
± 10 %
± 10 %
± 7 %
with If ≤ 6 In: ± 7
% / with If > 6 In:
± 10 %
ABB | SACE Emax 2
Trip time tolerance
(3)
with If ≤ 6 In: ± 10 % / with If > 6
In: ± 20 %
The best between ± 10% and 40
ms
with If ≤ 6 In: ± 15 % / with If > 6
In: ± 20 %
The best between ± 10% and 40
ms
--
The best between ± 10% and 40
ms
(2)
± 15 %
--
--
with t6 ≥ 5 s: ± 100 ms / with t6 <
5 s the best between ± 10 % and
± 40 ms
Trip time tolerance
The best between ± 10% and 40
ms
--
The best between ± 10% and 40
ms
The best between ± 10% and 40
ms
Ekip Touch - Protections
11 - Performance table

Advertisement

Table of Contents
loading

Table of Contents