Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply , either on the
Power supply Ekip Com EtherNet/IP
Interface the module has three signaling leds:
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
230 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
is supplied directly by the Ekip Supply module to which it is connected.
TM
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Figure 134
LED
Description
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Indicates the communication state:
Link (1)
• Off: incorrect connection, signal absent
• on fixed: correct connection
Indicates the communication state:
Activity (2)
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
is available in the Settings menu (page 49).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings - Modules menu:
Parameter
Static IP address ON
Static address IP address
Static Network Mask
Static Gateway address
2
Description
Defines whether the module has the dynamic (Off) or
static (On) IP address.
Se = On all the associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
When there are several subnets, enables the IP address
of the node to which the module is connected to be
selected
ABB | SACE Emax 2
1
Default
OFF
0.0.0.0
0.0.0.0
0.0.0.0
External electronic accessories
7 - Ekip Com EtherNet/IP TM