ABB SACE Emax 2 Series Operating Instructions Manual page 163

Low voltage air circuit-breaker
Table of Contents

Advertisement

Mechanical status indicators The following are the possible states in which you can find the circuit-breaker:
160 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
7.
Check that the circuit-breaker is open (open / closed indicator "O - OPEN"), and check that the
springs are discharged (spring signalling device "white - DISCHARGED SPRING") as indicated in
Figure 80.
Figure 80
1.
Circuit-breaker open with springs discharged (see Figure 81).
2.
Circuit-breaker open with springs charged (see Figure 82).
3.
Circuit-breaker closed with springs discharged (see Figure 83).
4.
Circuit-breaker closed with springs charged and not ready to close (see Figure 84). This state
occurs when after closing (see step 4 - Manual operations for opening and closing the circuit-
breaker) the springs are recharged manually or automatically by the gearmotor (if provided).
5.
Circuit-breaker open with springs charged and not ready to close (see Figure 85). This state occurs
in the following cases:
• The circuit-breaker is open due to tripping of protection trip units and the Reset signal has
not been reset. To close the circuit-breaker press the TU Reset pushbutton on the front of
the circuit-breaker.
• The key lock or padlock is active in the open position.
• The undervoltage coil is de-energized
• The opening coil is permanently energized.
• The closing coil is permanently energized.
• The pushbutton for enabling the insertion/extraction crank of a withdrawable circuit-brea-
ker is pressed.
Figure 81
Figure 84
Figure 82
Figure 85
ABB | SACE Emax 2
Figure 83
Mechanical characteristics
2 - E2.2-E4.2-E6.2 description

Advertisement

Table of Contents
loading

Table of Contents