ABB SACE Emax 2 Series Operating Instructions Manual page 175

Low voltage air circuit-breaker
Table of Contents

Advertisement

172 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
The connection for the E2.2-E4.2-E6.2 circuit-breakers is shown below as swell as the tables with some
examples of the amount and sizes of the connections that can be used for each type of circuit-breaker:
Figure 112 IEC
circuit-breaker IEC
60947
E2.2
E4.2
E6.2
values for spread terminals
(1)
circuit-breaker UL 1066
E2.2-A
E4.2-A
E6.2-A
Figure 113 UL
Dimension of busbars (mm)
Iu (A)
Horizontal terminals
800
1x50x10
1000
2x50x5
1250
2x50x10
1600
2x60x10
3x60x10
2000
3x60x10
(1)
3x60x10
2500
3x60x10
(1)
2000
2x80x10
2500
2x100x10
3200
3x100x10
4000
4x100x10
4000
4x100x10
5000
5x100x10
6300
6x100x10
Dimension of busbars (inches)
Iu (A)
Horizontal terminals
4x1/4x2
1600
3x1/4x2.5
2000
4x1/4x2.5
2000
4x1/4x2.5
2500
4x1/4x4
3200
-
3600
-
4000
4x1/4x5
5000
8x1/4x5
6000
-
ABB | SACE Emax 2
Vertical terminals
1x50x10
2x50x5
2x50x10
1x100x10
2x80x10
2x80x10
(1)
4x100x5
4x100x5
(1)
2x80x10
2x100x10
3x100x10
4x100x10
4x100x10
5x100x10
6x100x10
Vertical terminals
3x1/4x2
2x1/4x3
4x1/4x2
4x1/4x2
3x1/4x4
4x1/4x4
4x1/4x5
4x1/4x5
6x1/4x5
6x1/4x6
Continued on the next page
Mechanical characteristics
3 - Installation