Connecting The Bus Cable; Length Of Stripped Ends For Connection To Rs 485 Repeater - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

RS 485 repeaters: installing, connecting and operating
6.7

Connecting the bus cable

Cable type
Connecting the
SINEC L2 bus
cable
6-12
The SINEC L2 bus cable must satisfy the requirements laid down in
Section 5.3.
Connect the SINEC L2 bus cable to the RS 485 repeater as follows:
1. Cut the SINEC L2 bus cable to length.
2. Strip the ends of the SINEC L2 bus cable as shown in Fig. 6-10.
Fold back the braided shield over the end of the cable sheath. This is
necessary to ensure that the shield clamp can function as strain relief and
as a terminal for the shield.
6XV1 830–0AH10 (bus cable, solid)
6XV1 830–3BH10 (drum cable)
8.5
16
Ç Ç Ç
Ç Ç Ç
Ç Ç Ç
Braided shield must be folded back
Figure 6-10 Length of stripped ends for connection to RS 485 repeater
3. Connect the SINEC L2 bus cable to the RS 485 repeater:
Connect the same conductor (green/red for SINEC L2 bus cable) to the
same connections, A or B (e.g., always connect the green conductor to
terminal A and the red conductor to terminal B).
4. Tighten the shield clamps so that the naked shield is held firmly by the
clamp.
6XV1 830–3AH10 (buried cable)
10
16
Ç Ç Ç
Ç Ç Ç
Ç Ç Ç
8.5
ET 200 Distributed I/O System
16
10
EWA 4NEB 780 6000-02a

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Et 200

Table of Contents