IM 308-C master interface and memory card
Characteristics
3-14
The characteristics of the IM 308-C as DP slave are as follows:
For each IM 308-C as DP slave, the DP master can process up to
122 bytes inputs (DP slave outputs) and up to 244 bytes outputs (DP slave
inputs).
244 bytes outputs (DP slave inputs) is the maximum if all the outputs are
digital with byte consistency over module. For all other cases, see Table
3-10 (bus profile = PROFIBUS-DP).
The values in the table below (maximum consistent data lengths for the
IM 308-C as DP slave) are applicable only for high–speed load/transfer
commands in the slave CPU, e.g. TNB, TNW. The access time for load/
transfer commands must be as short as possible.
Table 3-10

Maximum consistent data lengths in bytes for IM 308-C as DP slave

Maximum consistent data lengths in bytes for IM 308-C as DP slave:
CPU
9.6
19.2
941A
55
30
941B
122
69
942A
57
31
942B
122
69
943A
106
57
943B
122
69
944A
122
122
944B
122
122
945
122
122
922
122
115
928A
122
122
928B
122
122
946/947
122
122
948
122
122
If the IM 308-C is DP master, see the values for maximum consistent data
lengths in Table 3-5 (Page 3-7):
An IM 308-C can be operated as:
– DP master
– DP slave
– DP master and DP slave (precondition: there must be at least two DP
masters on the bus)
Using COM ET 200 Windows, you can set a response monitoring time.
Baud rate in kbaud
93.75
187.5
500
1500
6
3
1
1
14
7
4
2
6
3
2
1
14
7
4
2
11
5
3
1
14
7
4
2
122
64
40
20
122
80
50
25
122
122
122
100
23
11
7
3
35
17
11
5
122
106
66
33
122
106
66
33
122
122
100
50
3000
6000
12000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16
15
11
20
18
14
83
75
58
3
2
2
4
4
3
27
25
19
27
25
19
41
37
29