Siemens SIMATIC S5 Manual page 212

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Error-reporting
If you selected "none" as the error-reporting mode in COM ET 200
mode "none"
Windows, ET 200 responds as follows:
Caution
!
If you selected "none" as the error-reporting mode, you can only detect an
error in the distributed I/O in the application program by means of diagnostic
analysis with the IM308C.
Consequently, we strongly recommend that "none" be selected as the
error-reporting mode only for initial operation.
Table 11-7 Reaction to interruption of bus communication or failure of a DP slave (error-reporting mode "none")
Failed DP
Reaction of CPU
slave(s):
slave(s):
Response
monitoring
No
CPU remains in
RUN
Yes
CPU remains in
RUN
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
Failed
DP slave
Reaction of failed DP slave(s):
Inputs in the CPU are set to "0",
outputs on the DP slave are ...
frozen.
set to "0" when response
monitoring time expires.
IM 308-C – starting ET 200
Remaining DP slaves
Reaction of remaining DP slaves:
The inputs in the CPU are
updated as before. The outputs
on the DP slaves are ...
updated as before.
updated as before.
11-13