Table 9-20 Meanings of the error numbers in the ERR parameter, continued
LOW byte
Meaning
of ERR
Hex.
Dec.
AB
171
TYP parameter invalid; specified
H
marker memory area M/S too short.
AC
172
FCT parameter invalid; FB IM308C
H
does not recognize specified function
AD
173
STAD parameter invalid
H
AE
174
Station number invalid (IMST
H
parameter)
AF
175
LENG parameter too large. The
H
IM 308-C does not have the desired
number of data bytes for the
specified DP slave.
B0
176
QVZ error; IM 308-C does not react. Check the IM 308-C (for reasons for QVZ, see Section 11.2).
H
B1
177
TYP parameter invalid; the specified
H
DB/DX No. is invalid.
B2
178
DPAD parameter invalid
H
C1
193
Error message from IM 308-C: The
H
requested command has already been
executed; the IM 308-C is out of
resources.
C2
194
Error message from IM 308-C: The
H
IM 308-C is in wrong mode.
C3
195
Error message from IM 308-C: No
H
appropriate group configured.
Error in the GCGR parameter setting
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
IM 308-C – addressing, diagnostics and use of the FB IM308C
The data to be transferred must fit entirely into the following
area:
Valid area for markers:
0
MB
Valid area for S markers:
0
SY
0
SY
The function must be entered in the KC format.
The validity range of the STAD parameter is as follows:
Valid range for markers:
0
STAD
Valid range for S markers:
0
STAD
0
STAD
The DP slave with the specified station number does not
exist.
Reduce LENG or select LENG = –1 (joker length).
Select DB/DX No.
The following are the only permissible addresses for this
parameter: F600, F800, FA00, FC00, FE00.
Only one CS or two GC commands possible at any given
time.
A control command can be executed only with the IM 308-C
in the RUN or CLEAR mode.
A control command can be executed only if an appropriate
group has been configured with COM ET 200 Windows.
Check syntax and content of the control command.
Remedy
199
1023 (CPU 928B)
4095 (CPU 946/947, CPU 948)
199
1023 (CPU 928B)
4095 (CPU 946/947, CPU 948)