The ET 200 distributed I/O system and lightning protection
D.2
How to protect the ET 200 distributed I/O system against
overvoltage
Rules for the 0
1
interface (potential
equalization in
lightning protec-
tion system)
D-4
Suitable measures for potential equalization in the lightning-protection
system at the interface between lightning-protection zones 0
follows:
Use twisted metal straps or metal braids of sufficient current-carrying
capacity as cable shields, e.g. NYCY or A2Y(K)Y, and ground these
straps at both ends;
or
lay the cables in
– continuously connected metal conduits grounded at both ends, or
– in reinforced-concrete ducts with continuous reinforcing members, or
– on enclosed cable trays made of metal and grounded at both ends.
or
use fiber-optic waveguides instead of lines which are capable of carrying
the surge current.