Maximum Consistent Data Lengths In Bytes For Im 308-C As Dp Master - Siemens SIMATIC S5 Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Data consistency,
The table below shows the maximum data lengths at which data consistency
IM 308-C as DP
is ensured. The length is automatically taken into account in parameterization
master
with COM ET 200 Windows.
244 bytes outputs (DP slave inputs) is the maximum if all the outputs are dig-
ital with byte consistency over module. For all other cases, see Table 3-5 (bus
profile = PROFIBUS-DP).
Table 3-5

Maximum consistent data lengths in bytes for IM 308-C as DP master

Maximum consistent data lengths in bytes for IM 308-C as DP master:
CPU
9.6
19.2
941A
122 (58)
122 (58)
941B
122 (58)
122 (58)
942A
122 (58)
122 (58)
942B
122 (58)
122 (58)
943A
122 (58)
122 (58)
943B
122 (58)
122 (58)
944A
122 (58)
122 (58)
944B
122 (58)
122 (58)
945
122 (58)
122 (58)
922
122 (58)
122 (58)
928A
122 (58)
122 (58)
928B
122 (58)
122 (58)
946/947
122 (58)
122 (58)
948
122 (58)
122 (58)
1
: Figures in parentheses are for IM 308-C release 2 and earlier
ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a
IM 308-C master interface and memory card
Baud rate in kbaud
93.75
187.5
500
41
20
15
94 (58)
47
35
42
21
16
94 (58)
47
35
79 (58)
39
29
94 (58)
47
35
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
79 (58)
59 (58)
122 (58)
118 (58)
88 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
1
1500
3000
6000
7
5
3
17
11
8
8
5
4
17
11
8
14
9
7
17
11
8
122 (58)
106 (58)
80 (58)
122 (58)
122 (58)
100 (58)
122 (58)
122 (58)
122 (58)
29
19
14
44
29
22
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
122 (58)
3
12000
3
7
3
7
6
7
66 (58)
83 (58)
122 (58)
12
18
111 (58)
111 (58)
122 (58)
3-7