ABB i-bus
KNX
Commissioning
No.
32
This communication object is enabled if in
set with the option yes.
This communication object consists of two bytes.
The high byte receives in coded form the current testing state of the emergency converter specified in the low byte. The
automatically status response will only send back for the selected emergency converter. The emergency test themselves is
triggered e.g. via the addressable communication object Emergency test result (No. 33) or the communication object Emer-
gency test trigger/status (no 168) per emergency converter.
The following numbering applies for the following list:
High byte
15
2
2
The bit number is identical with the exponent of the bit, e.g. number 2 complies with 2
Bit 0...5
Bit 6
Bit 7
Bit 8 and 10
Bit 11 and 12
Bit 13
Bit 14
Bit 15
Bit 14 and 15 show the status of an emergency converter. For a normal DALI device bit 6 and 7 are not calculated. For a
normal lamp or ballast failure group communication object no. 45 and coded communication object no. 20 are available.
Function
Emergency test status
14
13
12
11
10
9
8
2
2
2
2
2
2
= contains the binary number (0...63). This number corresponds to 1 added, to the number of the DALI
device to which the information in the High byte is related
= 0 determines status value relates to an individual device (converter).
= 1, status value request. If a telegram with a set bit 7 is received, it is interpreted as a status request of
the testing state and a corresponding feedback is sent. When the answer is sent, the value of bit 7 is re-
set to 0
= 000, no testing
= 001, functional test
= 010, partial duration test
= 011, duration test
= 100, battery request runs (does not require any time, and is not displayed for this reason)
= 101 and 110 without function or the evaluation of the request is not considered
= 111 It is no valid test status available or the DALI member do not support DALI emergency converter
according IEC 6286-202. The content of Bits 8 to 15 are invalid..
= 00, testing has ended positively
= 01, testing pending, not yet started
= 10, test runs
= 11, test interrupted
= 1, testing manually started
= 1, lamp fault (converter)
= 1, device (ballast/converter) fault
Communication object name
DALI output
Parameter window -
Emergency, page 39, the parameter Emergency test status is
Low byte
7
6
5
4
3
2
2
2
2
2
2
Data type
Flags
2 byte
C, R, T
non DPT
2
1
0
2
2
2
.
DGN/S 1.16.1 | 2CDC 507 114 D0201 115