3.2.6.2
Parameter window - Cx...Cy Test
In this parameter window, the emergency lighting converter test for a self-contained emergency lighting is
parameterized. The tests are triggered automatically via the emergency lighting converter or by the higher-
level control via the KNX and the DGN/S. The actual tests are undertaken by the emergency lighting con-
verter. The emergency lighting converter sends the test results on the DALI. The DGN/S transfers these
on the KNX. The test results are stored, issued and evaluated from the KNX on a control panel.
Note
The automatic testing sequence is an optional function of the DALI standard for emergency lighting
converters to EN 62 386-202. It must be tested in advance whether the emergency lighting converter
undertakes an automatic test. Otherwise it is possible to trigger the test by the higher-level control.
Note
Undertaking of the emergency lighting test cannot be guaranteed. The start of the test is a reserved
indicator that the test should be started as quickly as possible. If this is not possible for technical rea-
sons, the request remains active. The test starts at the next possible time. The corresponding state is
detected by communication object Emergency test trigger/status (no. 169).
DGN/S 1.16.1 | 2CDC 507 114 D0201 95