Parameter Window - Gx Sequence - ABB i-bus KNX Product Manual

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.2.2.8

Parameter window - Gx Sequence

The parameter window Gx Sequence is enabled in
ter Select additional function has been set to the option Sequence.
The DGN/S offers the possibility of allowing a sequence to be run. A sequence is a string of up to a maxi-
mum of ten scenes, which are recalled successively. The recall of the lighting groups involved is under-
taken via the communication object Switch or Switch/status of the lighting group. Furthermore, the set se-
quence can be repeated up to 255 times. If required, endless repetition of the sequence can be parameter-
ized. In this way, it is possible to program running lights on the device without additional logic or timer
modules, for example, for effect lighting, facade lighting, and in shop presentation or exhibition areas.
Note
Only one sequence can be programmed on the DGN/S. The setting is undertaken in the Sequence
parameter window. The function Sequence is recalled by a switch telegram from the lighting groups
which are members. This parameterization is undertaken in
For further information see: Sequence, page 142
With function Sequence, the lighting group follows the predefined sequence. The reaction to switch, dim-
ming or brightness value telegrams during function Sequence can be parameterized individually:
If in the following, the communication object Switch or Brightness value is mentioned, the details apply for
the communication objects Switch/status or Brightness value/status.
Hinweis
Is a central command e.g. switch, dimming or set brightness received via communication object DALI
output, the sequence function switch in standby and the central command is carried out.
74 2CDC 507 114 D0201 | DGN/S 1.16.1
Parameter window Gx
Group, page 51, if the parame-
Parameter window Gx
Group, page 51.