ABB i-bus
KNX
Commissioning
Period of partial test calculate with
rated time
Options:
The period for the partial test is independent of whether the partial duration test is triggered automatically
or manually via a communication object.
yes: The DGN/S reads from the emergency lighting converter the rated duration of the battery and
calculates (plus 10 % duration rating), from these values, the time duration for the partial duration test.
no: No automatic duration or partial duration test is intended for the emergency lighting converter.
For further information see:
With the option no, a further parameter appears:
Period of partial test
in 2x min [2...255]
Options:
This parameter defines the time duration of the partial test. The set value is multiplied by 2 in order
to obtain the result, e.g. with the default value 35 the partial duration test takes 70 minutes.
Trigger functional test automatically
Options:
yes: The emergency lighting converter starts the functional test automatically and passes on the in-
formation via the DALI to the DGN/S. The start of the functional test is executed in a fixed interval.
Note
Automatic starting of the functional test after a fixed interval is an optional function stated in the stan-
dard for an emergency lighting converter. It must be decided in advance whether the emergency lighting
converters should support the automatic testing properties.
no: No automatic functional test is intended for the emergency lighting converter.
With the option yes, a further parameters appear:
Test cycle in days [1...255]
Options:
This parameter determines the time interval that is automatically used by the function test with the
emergency lighting converter. The default value of 7 is set before delivery of the emergency lighting
converter.
96 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
Partial duration
test, page 10
2...35...255
yes
no
1...7...255