Communication Objects General - ABB i-bus KNX Product Manual

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.3.2

Communication objects General

No.
0
This communication object is enabled, if in the
is parameterized with the option send value 0/1 cyclically.
In order to regularly monitor the presence of the device on the KNX, an in operation monitoring telegram can be sent cyclically
on the bus.
As long as the communication object is activated, it sends a programmable in operation telegram.
1
The manual operation is inhibited via this communication object.
Telegram value:
With inhibited manual operation, it is not possible to manually switch the connected DALI devices via the DGN/S. Furthermore,
the function Detect ballasts is no longer possible via a long button push (> 5 s) of the button
At the same time, the status of manual operation can be read via this communication object, inhibited (1) and enabled (0) or
sent on the KNX.
2
This communication object is always enabled.
Telegram value:
If the DGN/S receives a telegram with the value 1 on this communication object, one-off DALI addressing is triggered. All DALI
devices that do not yet have a DALI address receive an address. DALI devices that have double addressing are removed. The
DALI addressing is described in section 4.1.
This function is particularly interesting when the parameterization forbids automatic DALI addressing (see
General, page 27). It is thus possible after a DALI device is exchanged to assign it a DALI address.
3
This communication object is enabled if in the
voltage" 1 Bit is set with the option yes.
If the gateway operating voltage fails for more than five seconds, a fault message telegram is sent immediately.
Telegram value:
4
This communication object is enabled if in the
is set with the option yes - acknowledgement is required.
This communication object enables both the reset of the Fault gateway supply and the lamp, ballast and DALI fault signals of
the individual lamp groups. The faults are only reset after acknowledgement if the reasons for the fault have been corrected
beforehand.
Telegram value:
Function
In operation
Parameter window
Manual operation block/status
0 = manual operation / button
1 = manual operation / button
Trigger DALI addressing
0 = no reaction
1 = trigger DALI addressing
Fault gateway supply
Parameter window
0 = no fault
1 = fault
Acknowledge faults
Parameter window
0 = no function
1 = reset faults
Communication object name
General
General, page 27, the parameter Send object "In Operation"
General
is enabled
is blocked
General
General
General, page 27, the parameter "Fault Gateway supply
General
General, page 27, the parameter "Acknowledge faults" 1 Bit
DGN/S 1.16.1 | 2CDC 507 114 D0201 101
Data type
Flags
1 bit
C, T
DPT 1.002
1 bit
C, R, W, T
DPT 1.003
.
1 bit
C, W
DPT 1.003
Parameter window
1 bit
C, R, T
DPT 1.005
1 bit
C, W
DPT 1.015