Communication Objects Function Staircase Lighting - ABB i-bus KNX Product Manual

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.3.10

Communication objects function Staircase lighting

If the additional function Staircase lighting is selected in the
lowing communication objects appear.
No.
41, 49...
153, 161
This communication object is enabled if in
enabled.
This communication object is used for activation/deactivation of the function Staircase lighting. With deactivation, the lighting
group behaves like a "normal" lighting group of the group-orientated DGN/S without function Staircase lighting. The function
Staircase lighting can be reactivated, if a telegram with the value 1 is received on the DGN/S via this object.
By setting the T flag, the communication object is actively sent after KNX voltage recovery.
Telegram value:
As long as function Staircase lighting is activated, the staircase lighting is initiated by a telegram with the value 1 to one of
both communication objects Switch or Switch/status.
In the
Parameter window - Gx Staircase lighting
dimming or scene telegram interrupts the function Staircase lighting.
For further information see:
134.
41, 49...
153, 161
This communication object is enabled if in
enabled and simultaneously in
Staircase lighting of the lighting group is programmed with the option yes: via object "Act. Staircase lighting/ Status".
In this case, the status of the function Staircase lighting is sent via this communication object on the KNX in addition to the
functions described above.
1)
The numbers of the communication objects apply for lighting groups 1...16.
128 2CDC 507 114 D0201 | DGN/S 1.16.1
Function
Activate fct. staircase lighting
1)
Parameter window Gx
0 = staircase light is deactivated
1 = Staircase light is activated and started
Parameter window - Gx Staircase
Act. staircase lighting/status
1)
Parameter window Gx
Parameter window - Gx Staircase
Parameter window Gx
Communication object name
Group x
Group, page 51, the additional function Staircase lighting is
on page 77, you can parameterize if a switch, brightness value, relative
lighting, page 77, or chapter
Group x
Group, page 51, the additional function Staircase lighting is
lighting, page 77, the parameter Status response of function
Group, page 51, the fol-
Data type
Flags
1 bit
C, W
DPT 1.003
Staircase
lighting, page
1 bit
C, W, R, T
DPT 1.003