ABB i-bus KNX Product Manual page 90

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Number of cycles
(0...255, 0 = not limited)
Options:
The sequence mode is triggered by an ON telegram with the value 1 on the communication object Switch
or Switch/status of a lighting group.
This parameter defines how often a sequence should be repeated.
0: The sequence is repeated continuously. An interruption can be performed in accordance with the
parameterization by an OFF telegram to one of the communication objects of the lighting group. The
setting is undertaken in the
1...255: This is the number of repetitions of a sequence. An interruption can be performed in accor-
dance with the parameterization by an OFF telegram to one of the communication objects of the light-
ing group. The setting is undertaken in the
1)
Step x
1)
x = 1 to 10 and represents a step in the sequence
Options:
This parameter determines the scene, which is used by the DGN/S, for step x of the sequence. This scene
is recalled during a sequence run or during its repetition as a brightness value for scene x. A scene can be
assigned to several sequence stages.
Note
In the scene, the brightness value and lighting groups, which are controlled with sequence step x, are
parameterized. The transition time is the speed, at which the brightness value is set, and the runtime is
the length of time, for which the brightness value is retained, and they are set with both the following
parameters (Transition time and runtime).
The Transition time for the scene parameterized in the parameter window Scene does not have an
influence on the course of the sequence.
Transition time, replaces transition
time in the scene
Options:
This parameter determines the time duration, in which the DGN/S approaches the brightness value
88 2CDC 507 114 D0201 | DGN/S 1.16.1
0, 1...255
Parameter window - Gx
Scene 1
...
Scene 14
jump to
0.7 s
2 s
...
90 s
for the scene step. The brightness value is defined in the parameter window (Scene value) Scene.
jump to: The lighting groups, which are defined for this sequence step, switch on immediately.
0.7 s...90 s: In this period, all lighting groups are dimmed to the parameterized brightness va-
lue.
Sequence, page 74.
Parameter window - Gx
Sequence, page 74.