ABB i-bus
KNX
Device Technology
2.4

Assembly and installation

The device is a modular installation device for quick installation in the distribution board on 35 mm mount-
ing rails to EN 60 715. The mounting position can be selected as required.
The electrical connection is implemented using screw terminals. The connection to the KNX is imple-
mented using the supplied KNX connection terminal. The terminal assignment is located on the housing.
The device is ready for operation after connection to the KNX voltage and the gateway operating voltage.
Accessibility of the devices for the purpose of operation, testing, visual inspection, maintenance and repair
must be provided compliant to VDE 0100-520.
Commissioning requirements
In order to commission the device, a PC with ETS and a KNX interface, e.g. USB or IP, are required. The
device is ready to operate when the KNX voltage and the gateway operating voltage are applied.
The assignment of the DALI devices to the lighting groups as well as the configuration of the emergency
lighting converter is undertaken with the DALI-Software-Tool.
The emergency lighting battery must be charged for commissioning of the DALI emergency lighting con-
verter. Commissioning without emergency lighting operation is not possible.
Important
Acceptance of the emergency lighting monitoring must be discussed with the corresponding approval
agency.
The installation and commissioning may only be carried out by qualified electrical specialists. The appro-
priate norms, guidelines, regulations and specifications for your country should be observed when plan-
ning and setting up electrical installations and security systems for intrusion and fire detection.
Protect the device from damp, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data limits!
The device should only be operated in an enclosed housing (distribution board)!
The voltage supply to the device must be switched off, before mounting work is performed.
Manual operation
The device incorporates manual operating features. The device features a button
of the DALI output.
16 2CDC 507 114 D0201 | DGN/S 1.16.1
for manual switching