Commissioning
3.2.2.6
Parameter window – Gx Slave emergency
This parameter is enabled if in
slave emergency (Object "Slave emergency active/status") has been parameterized with the option yes. In
this parameter window, the reaction of a functional lighting group with a slave emergency lighting situation
that is triggered by the communication object slave emergency active/status is defined. The prerequisite
for this is that the lamps can be controlled during slave emergency lighting operation via the DGN/S, i.e.
the are ready for operation via the DGN/S.
Brightness value of lighting group
during slave emergency
Options:
This parameter defines the brightness value of the lighting group in slave emergency lighting operation,
that is triggered by the communication object Slave emergency mode active/status. It is a prerequisite that
the lighting group can be controlled via the DGN/S.
Behaviour lighting group during
slave emergency
Options:
This parameter determines how the lighting group responds during slave emergency lighting when the
communication object Slave emergency active/status triggers slave emergency lighting operation. It is a
prerequisite that the lighting can be controlled via the DGN/S.
...not blocked: The lighting group is switched on at the start of slave emergency lighting with the
brightness value of the slave and is, however, not blocked. Switching telegrams via the KNX are trans-
ferred and implemented.
...blocked: The lighting group is switched on at the start of slave emergency lighting with the bright-
ness value of the slave and remains blocked, until the slave emergency lighting state has ended.
Switching telegrams received via the KNX are not implemented. After the end of slave emergency
lighting operation, the brightness value is set with the next parameter for the lighting group.
Important
If at least one of the 16 lighting groups is in slave emergency lighting and has been parameterized as
blocked, not only are the KNX group commands of the lighting groups blocked, but also all KNX broad-
cast commands for the DALI output.
68 2CDC 507 114 D0201 | DGN/S 1.16.1
Parameter window Gx
100 %(255)...1 %(1)
OFF and blocked
OFF and not blocked
unchanged and not blocked
Group, page 51, the parameter Enable with function