Commissioning
3.2.1

Parameter window General

In this parameter window, the main parameter settings relevant for the entire DGN/S are undertaken.
Enable manual operation. object
"Manual operation block/status" 1 bit
Options:
Using this parameter, the
tion object Manual operation block/status is available for this purpose
yes: The button
for between two and five seconds. In this mode, all DALI devices can be switched on and off to check
the cable connections and verify that they are correct. By pressing the button for longer than five sec-
onds the function Detect ballasts is triggered. In this way, the current number of connected DALI de-
vices is determined and saved as a reference value. Should this number change in the meantime, the
DGN/S will assume that there is a ballast fault. A ballast fault has also occurred if the DALI type
(emergency lighting converter/normal DALI device) of the DALI device has changed.
no: The button
yes
no
button on the front of the DGN/S can be blocked or enabled. The communica-
is enabled. By using button
is blocked. No manual action is possible on the device.
the test mode can be activated by pressing the button
DGN/S 1.16.1 | 2CDC 507 114 D0201 27