ABB i-bus
KNX
Commissioning
Status of remaining burn-in time
(coded)
Options:
The DGN/S features the option of being able to send the remaining burn-in time of any DALI device on the
KNX via the coded 2 byte communication object Remaining burn-in time (coded) (no. 30)
no: The remaining burn-in time is not made available on the KNX.
yes: The information concerning the remaining burn-in time is made available on the KNX. The com-
munication object Remaining burn-in time (coded) is enabled.
For further information see:
send object value via obj. "Remaining
burn-in time (coded)" 2 byte
Options:
38 2CDC 507 114 D0201 | DGN/S 1.16.1
Status response for different
status in the output:
Options:
Off
On
As every device has a burn-in counter and overlapping lighting groups are also possible, it is
possible that a lighting group may contain devices with different burn-in times. If this is the
case, this parameter can be used to define which state of the lighting group is reported.
On: If at least one connected device is in the burn-in state, the burn-in state is displayed
via the communication object Burn-in lamps/status with the value 1. No burn-in is re-
ported (value 0) if no lamps are burnt-in.
Off: If no lamps or only some of the lamps are burned in, the no burn-in state (value 0)
is indicated via the communication object Burn-in lamps/status. Only when all lamps of
the group are in the burn-in state is an active burn-in process indicated by the value 1.
yes
no
Communication object no.
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
30, page 114.