Mitsubishi Electric MELSEC iQ-R Series User Manual page 155

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Scaling enable/disable setting
Set whether to enable or disable the scaling.
For the scaling function, refer to the following.
Page 23 Scaling Function
Setting value
0
1
If a value other than the above is set, a scaling enable/disable setting range error (error code: 1A0H) occurs.
The scaling function cannot be used when the wave output function is used. In the channel for which Enable (0) is set while
the wave output function is being used, a scaling setting error in wave output mode (alarm code: 0B0H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling enable/disable setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is Disable (1) for all channels.
Scaling enable/disable setting [Q compatible mode]
When the Q compatible mode function is used, set whether to enable or disable the scaling.
The following shows the setting details in the Q compatible mode.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Scaling enabled, 1: Scaling disabled
(2) b4 to b15 of the R60DA4 and b8 to b15 of the R60DAV8 and R60DAI8 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Scaling enable/disable setting
CH1
CH2
502
702
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
CH2
53
Description
Enable
Disable
CH3
CH4
CH5
902
1102
1302
b1
b0
CH1
CH3
CH4
CH5
CH6
CH7
CH8
1502
1702
1902
CH6
CH7
CH8
APPENDICES
Appendix 3 Buffer Memory
A
153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60dav8R60da4R60dai8

Table of Contents