■For CLEAR setting
When the CPU module status is changed from RUN to STOP, the wave output is finished and the offset value is output. When
the CPU module status is changed from STOP to RUN, the value is output according to the setting in 'CH1 Output setting
during wave output stop' (Un\G524). The wave output does not resume.
To execute the wave output again, set Wave output stop request (0) to 'CH1 Wave output start/stop request' (Un\G462) after
changing the CPU module status from STOP to RUN. Then, change the value in 'CH1 Wave output start/stop request'
(Un\G462) from Wave output stop request (0) to Wave output start request (1).
CH1 D/A conversion enable/disable
setting (Un\G500)
CH1 Output enable/disable
flag (Y1)
CH1 Wave output start/stop request
(Un\G462)
CH1 Wave output status monitor
(Un\G401)
Wave data
Output set in CH1 Output setting
during wave output stop
(Un\G524)
1 FUNCTIONS
66
1.14 Wave Output Function
CPU module status
OFF
Wave output stop
request (0)
Wave output stop (0)
Analog output
Offset value
RUN
D/A conversion enable (0)
Wave output start
request (1)
Wave
output (1)
Wave output
stops.
The offset value
is output.
(1): Wave output starts when the value set in CH1 Wave output
STOP
RUN
ON
Wave output stop
request (0)
Wave output stop (0)
Wave output does not resume.
start/stop request (Un\G462) is changed from Wave output stop
request (0) to Wave output start request (1).
Wave output start
request (1)
Wave
output (1)
(
1)