CH1 Output value during wave output stop
This area is for setting the value to be output when Output value during wave output stop (2) is set in 'CH1 Output setting
during wave output stop' (Un\G524).
The setting for this area is enabled only in the wave output mode. In other modes, changing the setting value is ignored.
The setting range depends on the set output range. Configure the setting in the following range.
Output range
0 to 5V
1 to 5V
0 to 20mA
4 to 20mA
-10 to 10V
In the channel where a value out of the setting range is set, an output value during wave output stop setting range error (error
code: 1D3H) occurs and 'Error flag' (XF) turns on. The wave output does not start.
However, when a value other than Output value during wave output stop (2) is set in 'CH1 Output setting during wave output
stop' (Un\G524), the above error does not occur.
Since the default value is 0, change the setting value if 'CH1 Output setting during wave output stop' (Un\G524) is set to
Output value during wave output stop (2).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Output value during wave output stop
CH Output value during wave output stop
(When the Q compatible mode function is used)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
■Default value
The default value is 0 for all channels.
APPENDICES
160
Appendix 3 Buffer Memory
Setting range
0 to 32767 (practical range: 0 to 32000)
-32768 to 32767 (practical range: -32000 to 32000)
CH1
CH2
CH3
525
725
925
1016
1017
1018
CH4
CH5
CH6
1125
1325
1525
1019
1020
1021
CH7
CH8
1725
1925
1022
1023