Range setting [Q compatible mode]
This area is for setting an output range when the Q compatible mode function is used.
The following shows the setting details in the Q compatible mode.
Un\G402 (Range setting CH1 to CH4)
Un\G403 (Range setting CH5 to CH8)
(1) The buffer memory address 403 of R60DA4 is fixed to 0.
Output range
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
-10 to 10V
User range setting (voltage)
User range setting (current)
The output range cannot be changed for channels set to D/A conversion disabled. To change the output range, set the bit of
the corresponding channel of 'CH1 D/A conversion enable/disable setting [Q compatible mode]' (Un\G0) to D/A conversion
enabled (0), set 'CH1 Output enable/disable flag' (Y1) to OFF, and turn on and off 'Operating condition setting request' (Y9).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Range setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9) to enable the setting.
b15
...
b12 b11
...
CH4
CH3
b15
...
b12 b11
...
CH8
CH7
Setting value
R60DA4
0H
1H
2H
3H
4H
EH
FH
CH1
CH2
402
b8 b7
...
b4
b3
...
CH2
CH1
b8 b7
...
b4
b3
...
CH6
CH5
(1)
R60DAV8
0H, 2H
3H
4H
EH
CH3
CH4
CH5
403
b0
b0
R60DAI8
0H
1H
FH
CH6
CH7
CH8