Mitsubishi Electric MELSEC iQ-R Series User Manual page 47

Melsec iq-r digital-analog converter modul
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Wave output conversion cycle
The wave output conversion cycle is calculated by the following formula.
Conversion speed
Conversion cycle ( s)
=
In the wave output function, the conversion cycle can be set by setting 'CH1 Constant for wave output conversion cycle'
(Un\G531). The conversion cycle of the current output wave can be checked in 'CH1 Wave output conversion cycle monitor'
(Un\G432, 433).
Ex.
The conversion cycle and operation timing
Setting item
D/A conversion enable/disable setting
CH1 Constant for wave output conversion cycle
CH2 Constant for wave output conversion cycle
CH3 Constant for wave output conversion cycle
CH4 Constant for wave output conversion cycle
The following figure shows the conversion cycle of each channel with the above settings.
• CH1: 320s
• CH2: 640s
• CH3: 960s
• CH4: 1280s
D/A conversion is performed with this conversion cycle, and an analog value is output.
Wave output start
80µs
CH1: 320µs
320µs
CH2: 640µs
CH3: 960µs
CH4: 1280µs
Number of channels where
×
(80 s)
D/A conversion is enabled
320µs
320µs
320µs
320µs
640µs
640µs
960µs
1280µs
Constant for wave output
×
Setting value
D/A conversion enabled (0) for CH1 to CH4
1
2
3
4
320µs
320µs
320µs
320µs
640µs
640µs
960µs
960µs
1280µs
conversion cycle